Please update your Flash Player to view content.

Trailer #1 Electrical Requirements

Our bottling truck requires power from your winery as specified below

240 or 208 Volts, 3-Phase 60hz, with a dedicated circuit breaker of 60 amps.

A Cutler Hammer Part# NEMA-3R or equivalent, Service Disconnect Box, capabable of 60 amps 3-Phase, Non-Fusible Disconnect Box for 2 Guage wire with Grounding Lug.

NOTE: 3-Hot & 1-Ground.  Plus a Neutral.

A Dedicated Grounding Lug, large enough for 2-Gauge Wire.

AND/OR...

480 Volts at 30 amps, 3-Phase we have a dedicated circuit breaker of 30 amps.  We have a step down transformer onboard.

This disconnect box must be located within 100 feet of the Bottling Truck as we have 110 feet of cord to reach the winery.  Your local electrician will be able to install this for you.

If you're winery does not have a 240/3-Phase/60 amps or 480/3-Phase/30 amps power you may rent a generator from a local equipment rental company.  The equipment company will usually deliver and pick up, for your convenience.

We will hook up a Pigtail to the generator, to plug in to.

If you have any questions, please call our office at 707.252.8177.

 

Follow Us

  • Facebook Page: 222498701100757

Watch Us In Action

Bottling Video

Other Resources